100A LDZ14501000.100, 140A LDZ14501001.140, 200A LDZ14501002.200, 260A LDZ14501002.260
| Power Cell* | 70 A Cell | LDZ14501000.070 | G3 CELL NBH 70A 630V | 6SR3902-0AB00-0AM0 |
| 100 A Cell | LDZ14501000.100 | G3 CELL NBH 100A 630V | 6SR3902-0AC00-0AM0 | |
| 140 A Cell | LDZ14501001.140 | G3 CELL NBH 140A 630V | 6SR3902-0AD00-0AM0 | |
| 200 A Cell | LDZ14501002.200 | G3 CELL NBH 200A 630V | 6SR3902-0AE00-0AM0 | |
| 260 A Cell | LDZ14501002.260 | G3 CELL NBH 260A 630V | 6SR3902-0AF00-0AM0 |
B.4.2 15 Cell System Specifications Table B-5 15-Cell System Parameters Cells in Drive (without Redundancy) Output Voltage Available L-L (with O-M) Hp Range Power Cell Types (Continuous Current Rating) 15 6600 V 300-4900 40, 70, 100, 140, 200, 260, 315,375 A Parameters Ratings Input Line Voltage 2.4, 3.0, 3.3, 4.16, 4.8, 6.0, 6.3, 6.6, 6.9, 7.2, 8.4, 10, 11, 12, 12.47, 13.2, or 13.8 kV; 3 phase;+10% / -5% Input Frequency 50 or 60 Hz ±5% Input Power Factor > 0.95 above 10% load Input Harmonics <= 5% TDD with ambient THDv <= 2% Efficiency Copper Wound Transformer: 98% Transformer, 99% Converter, > 96,5% Total VFD Aluminium Wound Transformer: 97.5% Transformer, 99% Converter, > 96% Total VFD Output Voltage 6600 V Output HVF <0.03 Output dv/dt < 3000 V/µS Overload Capacity 110 % 1 minute / 10 minuteOutput Frequency & Drift1 0.5 - 330 Hz, ± 0.5 % (derates at <10 Hz and at >167 Hz) Output Torque 10 - 167 Hz rated torque (2 - Quadrant) Design Life 20 years Auxiliary Voltage 380 V - 400 V - 415 V, 50 Hz; 460 - 480 V, 575 V, 60 Hz; 3 phase2 Enclosure Type NEMA 1 Ventilated Degree of Protection IP21 (optional IP42) Ambient Temperature 0 - 40°C (maximum 50° C, derating starts from 40°C on) Altitude 0 - 3300 ft. without derating (maximum 12,300 ft with derating) Sound level 80 dB(A) Cooling Ventilated, forced air-cooled with integrated fans 1. For high speed projects (>300 Hz), consult Siemens concerning trade sanctions 2. Consult factory for availability of auxiliary voltages other than shown

B.4.1 9 Cell System Specifications Table B-4 9-Cell System Parameters Cells in Drive (without Redundancy) Output Voltage Available L-L (with O-M) Hp Range Power Cell Types (Continuous Current Rating) 9 4000 V (4160 V) 200-1100 40, 70, 100, 140 9 4000 V (4160 V) 800-2250 40, 70, 100, 140, 200, 260 9 4000 V (4160 V) 1500-3500 315, 375 Parameters Ratings Input Line Voltage 2.4, 3.0, 3.3, 4.16, 4.8, 6.0, 6.3, 6.6, 6.9, 7.2, 8.4, 10, 11, 12, 12.47, 13.2, or 13.8 kV; 3 phase;10% / -5% Input Frequency 50 or 60 Hz ±5% Input Power Factor > 0.95 above 10% load Input Harmonics <= 5% TDD with ambient THDv <= 2% Efficiency Copper Wound Transformer: 98% Transformer, 99% Converter, > 96,5% Total VFD Aluminium Wound Transformer: 97.5% Transformer, 99% Converter, > 96% Total VFD Output Voltage 9 Cell 2300 V 3000 V 3300 V 4000 V 4160 V Output HVF < 0.03 Output dv/dt < 3000 V/µS Overload Capacity 110 % 1 minute / 10 minuteOutput Frequency & Drift1 0.5 - 330 Hz, ± 0.5 % (derates at <10 Hz and at >167 Hz) Output Torque 10 - 167 Hz rated torque (2 - Quadrant) Design Life 20 years Auxiliary Voltage 200 V, 380 V - 400 V - 415 V, 50 Hz;230 V, 460 - 480 V, 575 V, 60 Hz; 3 phase2 Enclosure Type NEMA 1 Ventilated Degree of Protection IP21 (optional IP42) Ambient Temperature 0 - 40°C (maximum 50° C, derating starts from 40°C on) Altitude 0 - 3300 ft. without derating (maximum 12,300 ft with derating) Sound level 80 dB(A) Cooling Ventilated, forced air-cooled with integrated fans Technical Data B.4 System Specifications SINAMICS PERFECT HARMONY GH180 6SR41 manufactured in NMA Nuernberg, Germany 180 Operating Instructions Rev.201706301306

Cell Frame FRAME 2 Sizes 200 260 315 375 Weight 102.8 lbs 46.63 kg 112.6 lbs 51.07 kg 101.5 lbs 46.04 kg 131.6 lbs 59.69 kg Enclosure Width 13.99" 355.55 mm Enclosure Depth 25.88" 657.48 mm Enclosure Height 13.12" 333.17 mm Forced Air Cooling > 300 CFM (300-350 typical) > 425 CFM (425-450 typical) Note At ambient temperatures ranging from 40° to 50° C, the 140 A cell frame is limited to150 % - 1 minute/10 minutes overload with a 130 amp continuous rating.

B.3.1 Power Cell Specifications TableTable B-3 Power Cell Frame Size 1Cell Frame FRAME 1 Sizes 040 070 100 140 Output Nameplate Current 40 A 70 A 100 A 140 A Input Voltage 750 V ± 10%, 3 phase, 50/60 Hz Input Current 28 A 48 A 73 A 96 A Overload Capacity (see Note) (* Ambient <40°C) CL-1: 110% of nameplate 1 minute/10 minutes CL-2: 150% of nameplate 1 minute/10 minutes CL-3: 200% of nameplate 3 seconds/10 minutes Losses % 1.37 1.22 1.15 1.00 Discharge to 50 VDC (minutes) 0.84 1.68 2.53 3.37 Electrical Connections Rear access blind connection via power plugs Weight 52 lbs 23.58 kg 57.5 lbs 26 kg 63 lbs 28.6 kg 68.5 lbs 31 kg Enclosure Width 13.49" 342.8 mm Enclosure Depth 22.08" 560.98 mm Enclosure Height 10.25" 260.48 mm Forced Air Cooling > 180 CFM (225-250 typical)