9300 vector frequency inverter 0.37 ... 11 kW EVF9321-CVV003, EVF9322-CVV003
Basic devices in the power range 0.37 ... 11 kW Mounting with fixing rails (standard)
4
4.1 4.1.1
4.1 Basic devices in the power range 0.37 ... 11 kW
4.1.1 Mounting with fixing rails (standard)
Required mounting material from the scope of supply:
Description | Use | EVF9321 EVF9324 | EVF9325, EVF9326 |
Amount | |||
Fixing rails | Drive controller fixing | 2 | 4 |
Dimensions
9300vec114 |
Fig. 4.1-1 Standard mounting with fixing rails 0.37 ... 11 kW
囚 Drive controllers can be mounted side by side without spacing
9300 vector Type | Dimensions [mm] | ||||||||||
a | b | b1 | c | c1 | d | d1 | e 1) | g | k | ||
EVF9321-EV EVF9322-EV | 囚 | 78 | 384 | 350 | 39 | - | 365 | – | 250 | 6.5 | 30 |
EVF9323-EV EVF9324-EV | 囚 | 97 | 384 | 350 | 48.5 | - | 365 | – | 250 | 6.5 | 30 |
EVF9325-EV EVF9326-EV | 回 | 135 | 384 | 350 | 21.5 | 92 | 365 | – | 250 | 6.5 | 30 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables Mounting ƒ Attach the fixing rails to the housing of the drive controller.
EDSVF9333V EN 3.0-06/2005
4.1-1
4.1 4.1.2
Installing the basic device
Basic devices in the power range 0.37 ... 11 kW
Thermally separated mounting (push-through technique)
4.1.2 Thermally separated mounting (push-through technique)
For mounting in push-through technique, the drive controller of type EVF93xx-EV must be used. In addition, the mounting set for push-through technique is required.
Type | Mounting set | Type | Mounting set |
EVF9321-EV, EVF9322-EV | EJ0036 | ||
EVF9323-EV, EVF9324-EV | EJ0037 | EVF9325-EV, EVF9326-EV | EJ0038 |
Dimensions
Mounting cutout in control cabinet
![]()

![]()
Fig. 4.1-2 Dimensions for thermally separated mounting 0.37 ... 11 kW
9300 vector Type | Dimensions [mm] | |||||||||||
a | a1 | b | b1 | C | c1 | d | d1 | e 1) | f | g | ||
EVF9321-EV EVF9322-EV | 圓 | 112.5 | 78 | 385.5 | 350 | 60 | 95.5 | 365.5 | 105.5 | 250 | 92 | 6.5 |
EVF9323-EV EVF9324-EV | 圓 | 131.5 | 97 | 385.5 | 350 | 79 | 114.5 | 365.5 | 105.5 | 250 | 92 | 6.5 |
EVF9325-EV EVF9326-EV | 回 | 169.5 | 135 | 385.5 | 350 | 117 | 152.5 | 365.5 | 105.5 | 250 | 92 | 6.5 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
9300 vector Type | Dimensions [mm] | ||
Width | Height | ||
EVF9321-EV EVF9322-EV | 圓 | 82 | 350 |
EVF9323-EV EVF9324-EV | 圓 | 101 | 350 |
EVF9325-EV EVF9326-EV | 回 | 139 | 350 |
4.1-2
EDSVF9333V EN 3.0-06/2005
Basic devices in the power range 0.37 ... 11 kW Mounting in ”cold plate” technique
4
4.1 4.1.3
4.1.3 Mounting in ”cold plate” technique

The drive controllers can be mounted in ”cold plate” technology, e.g. on collective coolers. For this purpose, the drive controllers oftype EVF93xx-CV must be used.
Required mounting material from the scope of supply:
Description | Use | EVF9321 EVF9322 | EVF9323 EVF9324 | EVF9325 EVF9326 |
Amount | ||||
Fixing bracket | Drive controller fixing | 2 | 2 | 2 |
Sheet metal screw 3.5 × 13 mm (DIN 7981) | Mounting of fixing bracket to the drive controller | 6 | 6 | 6 |
Requirements for collective coolers
Ambient conditions
The following points are important for the safe operation of drive controllers:
ƒ Good thermal connection to the cooler
– The contact surface between collective cooler and drive controller must be at least as large as the cooling plate of the drive controller.
– Flat contact surface, max. deviation 0.05 mm.
– Connect the collective cooler with all specified screw connections with the drive controller.
ƒ Adhere to thermal resistance Rth given in the table. The values apply to the operation of drive controllers under rated conditions.
9300 vector Type | Cooling path | Drive controller earth | |
Power to be dissipated Pv [W] | Heat sink - surroundings Rth[K/W] | [kg] | |
EVF9321-CVV003 | 24 | 1.45 | 3.9 |
EVF9322-CVV003 | 42 | 0.85 | 3.9 |
EVF9323-CVV003 | 61 | 0.57 | 4.5 |
EVF9324-CVV003 | 105 | 0.33 | 4.7 |
EVF9325-CVV003 | 180 | 0.19 | 6.1 |
EVF9326-CVV003 | 360 | 0.10 | 6.1 |
ƒ The rated data and the derating factors at increased temperature also apply to the ambient temperature of the drive controllers.
ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.
4
4.1 4.1.3
Installing the basic device
Basic devices in the power range 0.37 ... 11 kW Mounting in ”cold plate” technique
Dimensions
Mounting

![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()

Fig. 4.1-3 Dimensions for mounting in ”cold plate” technique 0.37 ... 11 kW
9300 vector Type | Dimensions [mm] | ||||||||
a | b | b1 | c | c1 | d | e 1) | g | ||
EVF9321-CVV003 EVF9322-CVV003 | 囚 | 78 | 381 | 350 | 48 | – | 367 | 168 | 6.5 |
EVF9323-CVV003 EVF9324-CVV003 | 圓 | 97 | 381 | 350 | 67 | – | 367 | 168 | 6.5 |
EVF9325-CVV003 EVF9326-CVV003 | 回 | 135 | 381 | 350 | 105 | 38 | 367 | 168 | 6.5 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Apply heat conducting paste before screwing together the cooler and cooling plate of the drive controller so that the heat transfer resistance is as low as possible.
1. Fasten the fixing bracket with sheet metal screws 3.5 × 13 mm at the top and bottom of the drive controller 回.
2. Clean the contact surface of cooler and cooling plate with spirit.
3. Apply a thin coat of heat conducting paste with a filling knife or brush.
– The heat conducting paste in the accessory kit is sufficient for an area of approx. 1000 cm2.
4. Mount the drive controller on the cooler.
Basic devices in the power range 15 ... 30 kW Important notes
4
4.2 4.2.1
4.2 Basic devices in the power range 15 ... 30 kW
4.2.1 Important notes
The accessory kit is located in the inside of the drive controller.
Remove the cover of the drive controller
![]()

4.2.2 Mounting with fixing brackets (standard)
Mounting material required from the scope of supply:
Description | Use | Amount |
Fixing bracket | Drive controller fixing | 4 |
Raised countersunk head screw M5 × 10 mm (DIN 966) | Mounting of fixing bracket to the drive controller | 4 |
4
4.2 4.2.2
Installing the basic device
Basic devices in the power range 15 ... 30 kW Mounting with fixing brackets (standard)
Dimensions
|
9300vec111 |
Fig. 4.2-1 Standard mounting with fixing brackets 15 ... 30 kW
囚 Drive controllers can be mounted side by side without spacing
9300 vector
Type
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
b1
EVF9327-EV EVF9328-EV EVF9329-EV | 250 | 402 | 350 | 22 | 206 | 370 | 24 | 250 | 6.5 | 24 | 11 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Mounting ƒ Attach the fixing bracket to the heatsink plate of the drive controller.
Basic devices in the power range 15 ... 30 kW Thermally separated mounting (push-through technique)
4
4.2 4.2.3
4.2.3 Thermally separated mounting (push-through technique)
Dimensions
Mounting cutout in control cabinet
For mounting in push-through technique, the drive controller of type EVF93xx-EV must be used. In addition, the mounting set for EJ0011 push-through technique is required.
| |||||||||||||||
9300vec116 | |||||||||||||||
Fig. 4.2-2 Dimensions for thermally separated mounting 15 ... 30 kW | |||||||||||||||
9300 vector Type | Dimensions [mm] | ||||||||||||||
a | a1 | b | b1 | c1 | c2 | c3 | d | d1 | d2 | d3 | e 1) | e1 | g | h | |
EVF9327-EV EVF9328-EV EVF9329-EV | 279.5 | 250 | 379.5 | 350 | 19 | 131 | 243 | 361.5 | 32 | 100 | 97 | 250 | 159.5 | 6 | 9 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables | |||||||||||||||
9300 vector Type | Dimensions [mm] | ||||||||||||||
Width | Height | ||||||||||||||
EVF9327-EV EVF9328-EV EVF9329-EV | 236 | 336 | |||||||||||||
4.2 4.2.4
Installing the basic device
Basic devices in the power range 15 ... 30 kW Mounting in ”cold plate” technique
4.2.4 Mounting in ”cold plate” technique
Requirements for collective coolers
Ambient conditions

The drive controllers can be mounted in ”cold plate” technology, e.g. on collective coolers. For this purpose, the drive controllers oftype EVF93xx-CV must be used.
The following points are important for the safe operation of drive controllers:
ƒ Good thermal connection to the cooler
– The contact surface between collective cooler and drive controller must be at least as large as the cooling plate of the drive controller.
– Flat contact surface, max. deviation 0.05 mm.
– Connect the collective cooler with all specified screw connections with the drive controller.
ƒ Adhere to thermal resistance Rth given in the table. The values apply to the operation of drive controllers under rated conditions.
9300 vector Type | Cooling path | Drive controller earth | |
Power to be dissipated Pv [W] | Heat sink - surroundings Rth[K/W] | [kg] | |
EVF9327-CVV003 | 410 | 0.085 | 13 |
EVF9328-CVV003 | 610 | 0.057 | 13 |
ƒ The rated data and the derating factors at increased temperature also apply to the ambient temperature of the drive controllers.
ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.
Installing the basic device
Basic devices in the power range 15 ... 30 kW Mounting in ”cold plate” technique
4
4.2 4.2.4
Dimensions
Mounting
![]()
![]()
![]()


![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Fig. 4.2-3 Dimensions for mounting in ”cold plate” technique 15 ... 22 kW
EVF9327-CVV003 EVF9328-CVV003 | 234 | 250 | 381 | 350 | 110 | 220 | 367 | 171 | 6.5 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Apply heat conducting paste before screwing together the cooler and cooling plate of the drive controller so that the heat transfer resistance is as low as possible.
1. Clean the contact surface of cooler and cooling plate with spirit.
2. Apply a thin coat of heat conducting paste with a filling knife or brush.
– The heat conducting paste in the accessory kit is sufficient for an area of approx. 1000 cm2.
3. Mount the drive controller on the cooler.
Basic devices in the power range 45 ... 55 kW Important notes
4
4.3 4.3.1
4.3 Basic devices in the power range 45 ... 55 kW
4.3.1 Important notes
The accessory kit is located in the inside of the drive controller.
Remove the cover of the drive controller
![]()

4.3.2 Mounting with fixing brackets (standard)
Mounting material required from the scope of supply:
Fixing bracket |
Drive controller fixing |
4 |
Hexagon head cap screw M8 × 16 mm (DIN 933) | Mounting of fixing bracket to the drive controller | 4 |
Washer g 8.4 mm (DIN 125) | For hexagon head cap screw | 4 |
Spring washer g 8 mm (DIN 127) | For hexagon head cap screw | 4 |
4
4.3 4.3.2
Installing the basic device
Basic devices in the power range 45 ... 55 kW Mounting with fixing brackets (standard)
Dimensions
![]()
![]()
![]()
![]()
![]()


![]()
![]()
![]()
![]()
![]()
![]()
Fig. 4.3-1 Standard mounting with fixing brackets 45 ... 55 kW
囚 Drive controllers can be mounted side by side without spacing
9300 vector Type | Dimensions [mm] | ||||||||||
a | b | b1 | c | c1 | d | d1 | e 1) | g | k | m | |
EVF9330-EV | 340 | 580 | 510 | 28.5 | 283 | 532 | 38 | 285 | 11 | 28 | 18 |
EVF9331-EV | 340 | 672 | 591 | 28.5 | 283 | 615 | 38 | 285 | 11 | 28 | 18 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Mounting ƒ Attach the fixing bracket to the heatsink plate of the drive controller.
4.3-2
EDSVF9333V EN 3.0-06/2005
Basic devices in the power range 45 ... 55 kW Thermally separated mounting (push-through technique)
4
4.3 4.3.3
4.3.3 Thermally separated mounting (push-through technique)
For mounting in push-through technique, the drive controller of type EVF93xx-EV must be used. In addition, the mounting set for EJ0010 push-through technique is required.

![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Fig. 4.3-2 Dimensions for thermally separated mounting 45 ... 55 kW
![]()
![]()
![]()
a
a1
b
b1
c1
c2
c3
c4
d
d1
d2
e 1)
e1
g
h
EVF9330-EV EVF9331-EV | 373 | 340 | 543 | 510 | 45 | 137.5 | 217.5 | 310 | 525 | 45 | 145 | 285 | 163.5 | 7 | 9 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Mounting cutout in control cabinet
Basic devices in the power range 75 ... 90 kW Important notes
4
4.4 4.4.1
4.4 Basic devices in the power range 75 ... 90 kW
4.4.1 Important notes
The accessory kit is located in the inside of the drive controller.
Remove the cover of the drive controller
![]()

4.4.2 Mounting with fixing brackets (standard)
Mounting material required from the scope of supply:
Fixing bracket |
Drive controller fixing |
4 |
Hexagon head cap screw M8 × 16 mm (DIN 933) | For fixing bracket | 8 |
Washer g 8.4 mm (DIN 125) | For hexagon head cap screw | 8 |
Spring washer g 8 mm (DIN 127) | For hexagon head cap screw | 8 |
4
4.4 4.4.2
Installing the basic device
Basic devices in the power range 75 ... 90 kW Mounting with fixing brackets (standard)
Dimensions
|
9300vec134 |
Fig. 4.4-1 Standard mounting with fixing brackets 75 ... 90 kW
囚 Drive controllers can be mounted side by side without spacing
9300 vector
Type
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
b1
EVF9332-EV EVF9333-EV | 450 | 750 | 680 | 28.5 | 393 | 702 | 38 | 285 | 11 | 28 | 18 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Mounting ƒ Attach the fixing bracket to the heatsink plate of the drive controller.
4.4-2
EDSVF9333V EN 3.0-06/2005
Basic devices in the power range 75 ... 90 kW Thermally separated mounting (push-through technique)
4
4.4 4.4.3
4.4.3 Thermally separated mounting (push-through technique)
Dimensions
Mounting cutout in control cabinet
For mounting in push-through technique, the drive controller of type EVF93xx-EV. In addition, the mounting set for EJ0001 push-through technique is required.
![]()
![]()
![]()
![]()
![]()
![]()

![]()
![]()

![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Fig. 4.4-2 Dimensions for thermally separated mounting 75 ... 90 kW
EVF9332-EV EVF9333-EV | 488 | 450 | 718 | 680 | 49 | 172.5 | 295.5 | 698 | 49 | 200 | 285 | 164 | 9 | 10 |
1) For a fieldbus module plugged onto X1, consider mounting space for connecting cables
9300 vector | Dimensions [mm] | |
Type | A1 | b1 |
EVF9332-EV EVF9333-EV | 428.5 | 660 |